[YM8702]  Current voltage or RS485 proximity infrared temperature module

YM8702 YM8702 YM8702

Technical Parameters

Technical parameterParameter value
Temperature measurement range 0~+300℃ (Max 380℃)
Temperature measurement accuracy ±1 or %1 take the maximum value (maximum ±3℃)
Repeat measurement accuracy ±0.5 or %0.5 take the maximum value (maximum ±2℃)
Optical Resolution 1.6:1
Spectral range 18-14um
Response time 100ms
Emissivity0.96
InterfaceRS485/4-20mA/DC0-5V/DC0-10V
PowerDC12~24V 1A
DimensionsΦ24mm×80mm

Product Selection

    Product DesignRS485,4-20mA,DC0-5V,DC0-10VMultiple output methods, the products are divided into the following models depending on the output method.
Product model output method
YM8702BRS485总线
YM8702M4-20mA
YM8702V5DC0-5V
YM8702V10DC0-10V

Kit recommendation

YM8702

Why choose this product?

YM8702 YM8702 YM8702

Application solution

YM8702

Product List

YM8702

Pictures

YM8702 YM8702

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function Code Start Address Data Length Check Code
010300 0000 0184 0A
    For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address Function Code LengthData 1Check Code
0103 0200 79 79 A6
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value as 121, assuming the data magnification is 100, then the real value is 121/100=1.21, Others and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
4000100 00temperatureRead Only0~65535
4010100 64Model CodeRead/Write0~65535
4010200 65 total number of measuring points read/write 1~20
4010300 66device addressread/write1~249
4010400 67baud rateread/write0~6
4010500 68communication moderead/write1~4
4010600 69protocol typeread/write1~10

  For example, the range is 0~300℃, the analog output is 4~20mA current signal, temperature and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA)temperatureValue (℃) Calculation Process
40.0(300-0)*(4-4)÷(20-4)+0
518.8(300-0)*(5-4)÷(20-4)+0
637.5(300-0)*(6-4)÷(20-4)+0
756.3(300-0)*(7-4)÷(20-4)+0
875.0(300-0)*(8-4)÷(20-4)+0
993.8(300-0)*(9-4)÷(20-4)+0
10112.5(300-0)*(10-4)÷(20-4)+0
11131.3(300-0)*(11-4)÷(20-4)+0
12150.0(300-0)*(12-4)÷(20-4)+0
13168.8(300-0)*(13-4)÷(20-4)+0
14187.5(300-0)*(14-4)÷(20-4)+0
15206.3(300-0)*(15-4)÷(20-4)+0
16225.0(300-0)*(16-4)÷(20-4)+0
17243.8(300-0)*(17-4)÷(20-4)+0
18262.5(300-0)*(18-4)÷(20-4)+0
19281.3(300-0)*(19-4)÷(20-4)+0
20300.0(300-0)*(20-4)÷(20-4)+0
    As shown in the above formula, when measuring 8mA, current current is 79℃。
  For example, the range is 0~300℃, the analog output is 0~5V DC0-5Vvoltage signal, temperature and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V)temperatureValue (℃) Calculation Process
00.0(300-0)*(0-0)÷(5-0)+0
160.0(300-0)*(1-0)÷(5-0)+0
2120.0(300-0)*(2-0)÷(5-0)+0
3180.0(300-0)*(3-0)÷(5-0)+0
4240.0(300-0)*(4-0)÷(5-0)+0
5300.0(300-0)*(5-0)÷(5-0)+0
    As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 150℃。
  For example, the range is 0~300℃, the analog output is 0~10V DC0-10Vvoltage signal, temperature and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated DC0-10Vvoltage value. The list of commonly used values is as follows:
DC0-10Vvoltage(V)temperatureValue (℃) Calculation Process
00.0(300-0)*(0-0)÷(10-0)+0
130.0(300-0)*(1-0)÷(10-0)+0
260.0(300-0)*(2-0)÷(10-0)+0
390.0(300-0)*(3-0)÷(10-0)+0
4120.0(300-0)*(4-0)÷(10-0)+0
5150.0(300-0)*(5-0)÷(10-0)+0
6180.0(300-0)*(6-0)÷(10-0)+0
7210.0(300-0)*(7-0)÷(10-0)+0
8240.0(300-0)*(8-0)÷(10-0)+0
9270.0(300-0)*(9-0)÷(10-0)+0
10300.0(300-0)*(10-0)÷(10-0)+0
    As shown in the above formula, when measuring 5V, current DC0-10Vvoltage is 150℃。